High voltage DC contactor manufacturer - Changzhou Apollo Automobile Technology Co. Ltd

APL250A-HFD

Description:


    High voltage DC contactor apl250a-hfd, installation of processing cabinet 1.7 to 3.3N. M, contact installation torque 8.8 to 11n. M, maximum depth of internal thread 12.5mm

Model: apl250a-hfd


application scope:

high voltage main circuit, pre charging circuit, slow charging circuit, fast charging circuit, high voltage auxiliary system, etc. of new energy vehicles;High voltage main circuit system of charging pile;Wind power, photovoltaic and other power control systems

product features:


● small size, light weight, DC 450V maximum switchable current 2000a

● external energy saver keeps low power consumption

● with optional auxiliary contact, it is convenient to monitor the monitoring status of main contact

● the epoxy pouring sealing technology is adopted to fully seal the inner part of the product, so as to protect the coil and contact system from oxidation for a long time with high safety

● adopting permanent magnet arc blowing technology, the product has high reliability

● executive standard: GB/t14048.5-2017

model explanation:

1620628723383887.jpg

appearance and installation dimensions:

1620628258265784.jpg

coil working voltage (applicable to the whole temperature range):

NumberWorking voltage9-36VDC
1Maximum voltage36VDC
2Maximum pull-in voltage9VDC
3Minimum maintenance voltage7.5VDC
4Minimum release voltage6VDC
5Maximum surge current3.8A
6Mean holding current0.13A(12V)0.07A(24V)
7Maximum surge time130ms

technical parameters:

categoryparameterunitvalue
Main contactMain contact, contact form/A set of bridge type normally open
(double acting contact)
Operating voltage rangeVDC12—900
Maximum short circuit currentA2000A
Withstand voltageVAC≥4000(1mA)
Insulation resistance under DC 500V≥100
Standard contact resistance≤3
Auxiliary contactAuxiliary contact, contact form/A set of normally open (SPST-NO)
Maximum current of auxiliary contactsA30VDC 2A: 125VAC 3A
Minimum current value of laying contactmA8v 100mA
Maximum contact resistance of auxiliary contactsΩ30VDC 0.417Ω;125VAC 0.150Ω
lifetimeLoad life (30A/ 450V)times≥5000
Mechanical lifetimes2,000.00
And the release ofAnd the timems≤25
The maximum value of contact bounce
(after pulling only)
ms≤7
Release timems≤12
environmentShock, 11ms,1/2 sine wave, peak, suctionG≤50
Peak sinusoidal vibrationG≤20
Working temperature—40—+85
Operating humidity rangeRH%5—85
standard weight(Kg)≤0.45


Product electrical life curveContinuous energizing capacity curve:

1620628693428121.jpg

precautions for application:


the end of life of contactor, that is, the insulation strength between the leading out load ends is lower than 50 megohm at 500V DC of insulation meter

(1) do not touch the load terminal when the relay is energized,Beware of electric shock

(2) the load voltage should be cut off when the control circuit and non-metallic materials are subjected to withstand voltage test

(3) avoid installing the product in the place with strong magnetic field (transformer or magnet), or close to the object with thermal radiation

(4) do not touch the main lead-out terminal with foreign matters and oil stains, and the external lead-in wire terminal and the main lead-out terminal are in reliable contact, otherwise the terminal will be heated severely and the connecting cable will be melted

(5) in the action voltage test, do not make the voltage rise slowly, please drive the coil by step power supply

(6) the bolt locking torque of each installation part shall be controlled within the specified range.The locking torque of the nut at the load installation position is 7n. M;In principle, please do not use it when the stud torque of relay installation part is 8-9n. M

(7) it falls outside the relay and is impacted


You may need

Add or consult other products

APL300A-HFD
    

APL250A-HFD
    

APL200A-HFD
    

APL150A-24HFD
    

APL150A-12HFD
    

APL100A-24HFD
    

APL100A-12HFD
    

APL300A-HAD
    

Relevant information

Contactor/relay related news, technology and topics of discussion

Cause of overcu

2021-08-23

The overview an

2021-08-14

Direct point ar

2021-08-12

How to select d

2021-07-22

Use ceramic sea

2021-07-12

Dc contactor ty

2021-07-09

Dc contactor co

2021-07-06

Dc contactor ar

2021-07-03